Aller au contenu

Fiche vulnérabilité

CVE-2023-2071 : faille critique Rockwell Automation Fa (CVSS 9.8)

Description

Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets.  The device has the functionality, through a CIP class, to execute exported functions from libraries.  There is a routine that restricts it to execute specific functions from two dynamic link library files.  By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.

En bref

Sévérité
Critique (CVSS 9.8)
Vecteur CVSS
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Exploitation active
Non signalée par la CISA
Publication
12 sept. 2023
Dernière mise à jour
25 sept. 2024

Produits concernés

  • Rockwell Automation Fa

Correctif et mesures

* Install the security patches for the respective versions referencing BF29493 - Patch: FactoryTalk Linx CIP Vulnerability issue, FactoryTalk View ME 12.0, 13.0 https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1139946 .

Références

Rechercher une autre vulnérabilité dans la base CVE